Delta inverter long-term idle points for attention
Published:2023-05-05 11:07:30
After the frequency converter is used for more than half a year, if the equipment is to be run again, the chance of damage may be greatly increased because of the placing environment, the service life of the frequency converter, the load rate and other factors. The fault usually presents the following problems:
1. After the equipment is energized, the inverter explodes and the front circuit breaker jumps.
2. After startup, there is no display on the panel of frequency converter
3. The frequency converter operates normally after startup, but fails after operation
4. The frequency converter operates normally after startup, but it presents a blast machine after operation
Why does the above phenomenon of frequency converter failure occur?
1. Improper placing environment of frequency converter will lead to the above problems.
2. Frequency converter is composed of rectifier module, IGBT and electrolytic capacitor and other primary components. If the electrolytic capacitor is not energized for a long time, the electrolyte in the electrolytic capacitor will dry up, so that the capacity will decrease and the leakage will increase. In this way, when the converter is powered, the operation of the switching power supply will be abnormal or damaged. In serious cases, it will lead to the damage of the electrolytic capacitor of the main circuit, resulting in the blasting of the converter.
Why are some frequency converters still able to be used normally after being placed for a period of time?
1. Frequency converter storage environment is perfect
2. The frequency converter does not work in overheat or overload condition for a long time
3. The service life of frequency converter is short
4, the capacitor characteristics of the frequency converter is better than **
How to guard against frequency converter power-on failure?
1, Frequency converter is not used for a long time, should be sealed in a dust-proof and moisture-proof environment, storage temperature is -25c-65c.
2. It is safer and more useful to use special equipment to charge the inverter regularly (every 3 months) and check the input and output ports. The 220 volt voltage is supplied to the 380 volt converter (110 volts is supplied to the 220 volt converter), and the voltage slowly rises from 0 volts to 220 volts. The duration is determined by the power of the converter. Then, supply 380 volts (220 volts) to the converter and look at the input voltage. Only an imbalance of +/-3% is allowed.
-
202212-29
The composition of the configuration software of Kunlun MCGS embedded version
The user system generated by MCGS embedded version is composed of five parts: main control window, device window, user window, real-time database and operation strategy.1, the main control window: the···
-
202301-12
Delta UPS uninterruptible power supply basic conditions
1. Visually inspect the UPS and battery (or other energy storage) equipment for obstructions and properly cool the surrounding area.2. Ensure that there is no abnormal operation or warning on the UPS ···
-
202307-07
LS PLC use introduction
1, for switching quantity controlThe ability of PLC to control the switching quantity is very strong. The number of points controlled by the input and output points, as few as a dozen points, dozens o···
-
202212-29
Schneider small circuit breaker and leakage switch difference
1. Definition of mini circuit breakerElectrical occupation for short MCB, suitable for communication 50/60Hz extra voltage 230/400V, extra current to 63A line overload and short circuit maintenance, a···
-
202303-02
Mitsubishi Inverter alarm history confirmation and clearance
When the FR-CS80 converter detects an anomaly, it will display fault information or alarm in the operation panel according to the abnormal content, or maintain functional action and block the output o···