Technical data
SIMATIC S7-1500, Digital volume output module DQ 16x 230V AC/2A ST; Relay 16 channels, divided into groups, each group of 2; 4A each group; Switch operation cycle counter for integrated relays, diagnostics; Alternative values: Modules support safe disconnection of load groups to SIL1 according to ENIEC 62061:2021 and Category 2 / PL c according to EN ISO 13849-1:415. Front connectors (screw type terminals or in-line) are ordered separately
General information
Product Type Mark DQ 16x 230 V AC/2 A ST (Relay)
Hardware function status FS01
Firmware version V1.1.0
● Updatable firmware is
Product function
● I&M data is; I&M0 to I&M3
● Clock synchronization mode No
● Start by priority yes
packaged
● STEP 7 TIA port, configurable/integrated, since version V13 SP1 / -
● STEP 7 Configurable/integrated, since version V5.5 SP3 / -
● PROFIBUS version GSD Edition/GSD revision V1.0 / V5.1
● PROFINET version GSD version/GSD revision above v2.3 / -
Operating mode
● DQ is
● DQ with energy-saving function No
● PWM No
● Oversampling no
● The MSO is
● Integrated operation cycle counter is; FW V1.1.0 or later
Supply voltage
Rating (DC) 24 V
Allowable range, lower limit (DC) 19.2 V
The upper limit (DC) is 28.8V
Reverse polarity protection is
Input current
Consumption current, maximum 185 mA
Output voltage/heading
Rating (AC) 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC
power
The power output from the backplane bus is 0.8 W
Power loss
Power loss, typical value 5 W
Digital output
Digital output type relay
Number of output terminals 16
M switch is
P switch is
The programmable digital output is
Short circuit protection No
Control digit input is
Motor starter with NEMA protection grade maximum specification 5
Output on-off capability
● Maximum lighting load: 50 W (230 V AC), 5 W (24 V DC)
Output current
● For signal "1" rating 2 A
● For the allowable range of signal "1", the minimum value is 10 mA; 10 V
● For the allowable range of signal "1", the maximum 2 A; Continuous thermal current
● For the residual current of signal "0", the maximum is 0 A
The two outputs are in parallel
● For logical connection
● Used to increase power No
● For redundancy control load is
Switching frequency
● The maximum value of resistance under load is 1 Hz
● The maximum value of inductive load is 0.5Hz
● The maximum value under lighting load is 1 Hz
Total current at the output
● The maximum current of each channel is 2 A; See additional instructions in the manual
● The maximum current of each group is 4 A; See additional instructions in the manual
● The maximum current of each module is 32 A; See additional instructions in the manual
Relay output terminal
● The number of relay outputs is 16
● Relay coil L+ (DC) power supply voltage 24 V
● The consumption current of the relay (coil current of all relays), typical. 150 mA
● External fuse B10 / B16 mini circuit breaker at relay output
● Contact circuit (internal) No
● The maximum number of operation cycles is described in the additional instructions in the manual
● No relays that are UL 508 approved
The on-off capacity of the contact
-- the maximum value of inductive load 2 A; See additional instructions in the manual
-- The maximum value of resistance under load is 2 A; See additional instructions in the manual
Conductor length
● Shielding, maximum 1 000 m
● Unshielded, maximum 600 m
Alarm/diagnosis/status information
The accessible alternative value is
alarm
● Diagnostic alarm Yes
● Maintenance alarm is
diagnosis
● Power supply voltage monitoring is
● Disconnect No
● Short circuit No
Diagnostic display LED
● RUN LED Yes; Green LED
● ERROR LED Yes; Red LED
● MAINT LED Yes; Yellow LED
● Power supply voltage monitoring (PWR-LED) is; Green LED
● Channel status display is; Green LED
● Used for channel diagnosis
● For module diagnosis is; Red LED
Potential isolation
Potential separation of channels
● Between channels no
● Between channels, group the number of points 2
● Between the channel and the backplane bus
● Between the channel and the load voltage L+
The allowable potential difference
250 V AC between different circuits, channels and L+ supply voltage between; 250 V AC, between channel and backplane bus; 500 V AC, between channels
insulation
Insulation test, using between channels: 3100 V DC, between channels and backplane bus: 3100 V DC, between L+ and backplane bus: 707 V DC (test type)
Standards, licenses, certificates
Applicable to security function No
Standard components for safety shut-off are; FS02 or later
Safety off The maximum level of safety that a standard component can achieve
● The performance rating complies with ISO 13849-1 PL c
● The class complies with ISO 13849-1 Class 2
Environmental requirements
Operating ambient temperature
● Horizontal installation, minimum value -25 °C; FS02 or later
● Horizontal installation, maximum 60 °C
● Vertical installation, minimum value -25 °C; FS02 or later
● Vertical installation, maximum 40 °C
dimension
Width 35mm
Height 147mm
Depth 129 mm
weight
Weight, about 350 g
FAQ
1.Who are We?
Beijing Zhongping Technology Co., LTD., is a one-stop integrated service provider of intelligent manufacturing, belongs to the Gong Doctor Group, is a scientific research, design, marketing, technical services, industrial Internet, international import and export services as one of the science and technology companies.
2.What can you buy from us?
PLC, inverter, human-machine interface, hydraulic products, low-voltage power distribution, industrial robots and core components
3.Is the item in stock or need to be purchased from another supplier?
We have a large inventory of goods and have our own warehouse.
4.What advantages do we have over other suppliers?
Our company has a large amount of inventory and a number of warehouses, but also in the country's important industrial provinces and cities with offices and a number of overseas service points. To provide you with intelligent manufacturing one-stop comprehensive services, save efforts, labor and cost.
5.Can you provide 100% new original authentic products?
We only sell new original genuine, no renovation, no fake, only for the original factory original!
6.How long is the delivery time?
If there is a stock, it will take 2-3 working days to ship, if the quantity is large, it will take 5-7 working days after receiving the payment, if it is not a conventional model, it will take some time, we will inform you of the specific delivery time.
7.Is there technical support available?
Of course, we have a professional technical team that can help you solve technical problems.
8.How do we guarantee quality?
We have three processes to control the quality of goods.
1). Our engineers will inspect the production and quality control in the factory regularly.
2) Incoming materials shall be inspected by experienced purchasing engineers before they can be stored.
3). At least 2 people in the logistics department cross-check the goods to be sent before delivery.
9.Can you guarantee the safe and reliable delivery of your products?
Yes, we strictly adopt the international standard packing. We also use special packaging for dangerous goods, and refrigerated shipping for items with temperature requirements. Special item packaging and general cargo standard packaging requirements may incur additional costs.
10.How about the freight?
The cost depends on how you choose to get the goods. Express is usually the fastest but also the most expensive way. Sea freight is the best solution for large quantities of goods. The exact shipping cost depends on the purchase amount、quantity and weight of your order. Please feel free to contact us for more information.