The alarm code cause and diagnosis method of the cabinet air conditioner of Rittal
Published:2023-07-07 09:29:33
Alarm code: A01
System message: Open the cabinet door
Air conditioning cause: The opening and closing position is incorrect
Diagnostic method: Check the transition position of the door and, if necessary, check the connection status
Alarm code: A02
System message: The temperature inside the cabinet is too high
Cause: The cooling capacity is too low or the sequence error message of smaller air conditioners is from A03 to A07
Diagnostic method: Check the cooling capacity
Alarm code: A03
System messages: Filter monitoring
Cause: The filter is dirty
Diagnosis: Clean or replace the air conditioner
Alarm code: A04
System message: Ambient temperature is too high/too low
Cause: The ambient temperature allowed range of 10 degrees to 60 degrees
Diagnosis: Raising or lowering the ambient temperature (e.g. heating or ventilating the room)
Alarm code: A05
System message: Ice
Cause: According to the operation mode, icing display
Diagnosis Method: Increase the normal temperature in the cabinet RITTAL cabinet (rittal cabinet)
Alarm code: A06
System message: PSA (High Voltage switch) monitor
Causes: The ambient temperature is too high, the condenser is dirty, the condensation filter is dirty, the condensation fan is broken, the expansion valve is broken, and the PSA (high pressure switch) monitor is broken
Diagnosis: The air conditioner high pressure exceeds the limit, clean the condenser or replace the filter, replace the condensing fan, expansion valve and PSA monitor should be repaired or replaced by engineers
Alarm Code: A07 System Message: Evaporator
Cause: Cooling failure
Diagnosis: Repair by refrigeration engineer
Alarm code: A08
System message: condensate alarm
Cause: Only some condensation in the air conditioner evaporates
Diagnosis: Check the condensate discharge and clean the foreign matter in the hose
-
202307-07
LS PLC use introduction
1, for switching quantity controlThe ability of PLC to control the switching quantity is very strong. The number of points controlled by the input and output points, as few as a dozen points, dozens o···
-
202302-20
This section describes how to set the bios after the Advantech 610l is powered on
1. Press Del to enter BIOS Settings. The following main menu is displayed.2. Select the IntegratedPeripherals TAB and press Enter to enter the menu below.3. Select SupperlODevice and press Enter to ac···
-
202302-24
WEINVIEW prompts the solution to the download mode error
1. Software editing - System Parameter setting -HMI attribute - Port number: 8000 Change, such as 9000;2. Call up the computer Task Manager -- end the process com_e30.exe;3. Restart the computer;4. Qu···
-
202301-12
Delta PLC maintenance knowledge introduction
1. Delta PLC power-on running light is not on, ERROR flickers, the possible cause is: no program2. Delta PLC can not communicate with the computer, which may be: RS23 is bad3. If the power indicator o···
-
202410-21
Input and Output Modules: Everything You Need to Know
I/O modules(input/output modules)manage the communication between the CPU and the network,including data transfer,power load management,and machine function control.It enables system integrators to co···