Does the supply cable between the Siemens soft starter and the motor need shielding
Published:2023-02-06 16:12:46
For 3RW soft starters, it is sufficient to use an unshielded main loop cable between the motor and the 3RW soft starter.
The main reasons are as follows:
The frequency of the power supply on the motor terminal is steady at 50 or 60 Hz throughout the soft starter operation
After the soft start is complete, the main loop switches to the internal bypass contactor in parallel, and the current and voltage waveforms are perfect sine waves.
The soft starter is operated using phase Angle control during soft start and soft stop. Phase Angle control achieves the purpose of step-down starting by controlling the thyristor turn-on time. Only when the pulse triggers the thyristor turn-on, the harmonic wave will be generated, and the duration is very short. So it's negligible.
-
202301-28
Siemens SINAMICS GM150 Deep Maintenance
On-site maintenanceCheck and clean pre-charge loop, rectifier unit, diode characteristics, inverter unit, GSV, AVT.Rectifier module diagnostic test, and high voltage switchgear interface function test···
-
202212-29
The composition of the configuration software of Kunlun MCGS embedded version
The user system generated by MCGS embedded version is composed of five parts: main control window, device window, user window, real-time database and operation strategy.1, the main control window: the···
-
202308-31
What are the applications of CASAPPA synchronous motors?
1, as a flow distribution device, according to the system requirements to distribute the output flow of the pumpIf the shaft is equipped with multiple sets of plain bearings, it is required to ensure ···
-
202309-07
YOULI Multiway valve - Multiway valve regulation method
1. Under normal conditions, before the hydraulic multiway valve leaves the factory, its opening pressure should be adjusted one by one to the setting value required by the user. If the user puts forwa···
-
202304-14
Delta inverter to reduce the failure rate method
Daily check Item 1 of Delta Frequency converter problem repair:Check whether the sound of the motor is abnormal during operation, including whether the motor is vibrating during operation.Daily view o···