Delta PLC maintenance knowledge introduction
Published:2023-01-12 16:46:44
1. Delta PLC power-on running light is not on, ERROR flickers, the possible cause is: no program
2. Delta PLC can not communicate with the computer, which may be: RS23 is bad
3. If the power indicator of Delta PLC is off, the power supply is bad
4 Delta PLC needs to send pulse should select the output transistor type PLC
5. Delta PLC output indicator light on, but no output: output point is broken
6. Delta PLC input cable is normal, the input terminal is closed, but the input indicator is off: the input point is bad
8. Power on Delta PLC BAT.LOW on: The battery is low
10. Delta PLC power-on burning power supply insurance: short circuit of the power board
11. All indicators of Delta PLC are normal, and all output points cannot operate: output expansion IC is broken
12. All the indicators of Delta PLC are normal, and the input contacts do not respond: RS232 is broken
13 Delta PLC simulation quantity has what control mode: temperature, liquid level
14 Delta PLC external communication port: RS232, RS485
15. Delta PLC voltage drops to the lower limit of voltage how to do: timely replacement
16. Delta PLC running light is not on, program input is normal, running switch has been closed, what is the reason: CPU bad
17. Delta PLC has 24V output but the power indicator is off: +5V power circuit is abnormal
18. Which Delta PLC can not be extended: DVP-EC3
19. Is Delta weighing module extended on the left side or the right side? Left side
20. The output pulse of DVP20PM00M can reach: 500HZ
-
202303-08
Cause of frequent trip of Schneider leakage switch
1. Bad deviceEach pile lead wire is not firmly connected, long-term loose, will cause the pile head heat, oxidation, burn the outer insulation of the wire, and announce the spark and coke taste, the f···
-
202302-08
Reduce Schneider inverter interference measures
(1) Inductance and capacitance are added on the input side of Schneider inverter to form LC filtering network.(2) The power line of Schneider inverter is directly supplied from the transformer side.(3···
-
202302-06
Siemens Soft Starter 3RW44 can self-reset can be fault
Not all faults can be self-reset. The faults that can be self-reset are as follows (The method of self-reset is to set the corresponding parameters in the menu of the LCD screen) :1) Motor thermal mod···
-
202301-12
Delta PLC maintenance knowledge introduction
1. Delta PLC power-on running light is not on, ERROR flickers, the possible cause is: no program2. Delta PLC can not communicate with the computer, which may be: RS23 is bad3. If the power indicator o···
-
202302-27
Delta servo motor how to choose?
In the selection of Delta servo motor, in principle should be based on the load conditions to choose. There are two kinds of loads on the motor shaft, namely damping torque and inertia load. The two l···