Fault detection methods for Omron relays
Published:2023-04-21 16:02:21
Fault detection Method One
1. You can first check whether the voltage of the Omron relay is high or low. Generally, the maximum voltage is between 180V and 240V.
Fault detection Method two
2. In addition, when the Omron relay fails, the first thing to check is the external connection of the relay, to see whether the connection of the relay contacts is wrong or broken, falling off or other abnormal phenomena.
Fault detection Method three
3. Next, you can check the power supply circuit of Omron relay and use the meter to test whether the voltage of positive and negative power supplies is the same. If the voltage value measured is the same, it can be inferred that the relay is normal. If the voltage is not a problem, then the power amplifier delay and protection circuit can be carried out.
Fault detection Method four
4. At this time, the Omron relay also needs to measure the power amplifier's final circuit. You can visually check whether there are components burned. Need to be further measured, power amplifier tube emission stage resistance to the ground has DC voltage (normal value is within 0.7V) if there is DC voltage that is generally the power amplifier at the end of the circuit problem, then the treatment method can only replace a power amplifier tube emission stage resistance.
Omron relay note instructions
1. When installing Omron relay, it must not be pushed in too hard, so as not to damage shafting and code plate. The OMRON relay should be gently pushed into the bushing shaft.
2. When using the Omron relay, it is necessary to check whether the plate spring is loose relative to the Omron relay and whether the screw of the relay is loose, so as to avoid some faults and other accidents in the process of operation.
3. Do not randomly connect the terminal between the Omron relay to the wrong, otherwise it is easy to cause the damage of the Omron relay in power-on operation.
-
202301-17
ABB's four control modes for industrial robots
I. Point control mode (PTP)This control mode only controls the position of discrete points specified by the end effector of industrial robots in the workspace. When controlling, only the industrial ro···
-
202302-01
Maintenance points of Omron relay
1. The shell surface of the Omron relay used in installation should be free of scratches, cracks and damage. In case of serious damage, the intact relay with the same specifications should be replaced···
-
202301-16
TPC1561HI MCGS on-state touch screen operation panel common faults
TPC1561HI MCGS touch screen operation panel common faults(1) Black screen, flower screen and white screen(2) LCD screen aging, low high pressure, lamp aging(3) The LCD screen has no display, and the b···
-
202302-06
Does the supply cable between the Siemens soft starter and the motor need shielding
For 3RW soft starters, it is sufficient to use an unshielded main loop cable between the motor and the 3RW soft starter.The main reasons are as follows:The frequency of the power supply on the motor t···
-
202302-07
WEINVIEW TK6070ih touch screen into the system setting what are the methods?
1. Generally, there is a small black arrow button in the lower right corner of the touch screen. After clicking and entering the correct password, you can enter the system Settings. However, during co···