Fault detection methods for Omron relays
Published:2023-04-21 16:02:21
Fault detection Method One
1. You can first check whether the voltage of the Omron relay is high or low. Generally, the maximum voltage is between 180V and 240V.
Fault detection Method two
2. In addition, when the Omron relay fails, the first thing to check is the external connection of the relay, to see whether the connection of the relay contacts is wrong or broken, falling off or other abnormal phenomena.
Fault detection Method three
3. Next, you can check the power supply circuit of Omron relay and use the meter to test whether the voltage of positive and negative power supplies is the same. If the voltage value measured is the same, it can be inferred that the relay is normal. If the voltage is not a problem, then the power amplifier delay and protection circuit can be carried out.
Fault detection Method four
4. At this time, the Omron relay also needs to measure the power amplifier's final circuit. You can visually check whether there are components burned. Need to be further measured, power amplifier tube emission stage resistance to the ground has DC voltage (normal value is within 0.7V) if there is DC voltage that is generally the power amplifier at the end of the circuit problem, then the treatment method can only replace a power amplifier tube emission stage resistance.
Omron relay note instructions
1. When installing Omron relay, it must not be pushed in too hard, so as not to damage shafting and code plate. The OMRON relay should be gently pushed into the bushing shaft.
2. When using the Omron relay, it is necessary to check whether the plate spring is loose relative to the Omron relay and whether the screw of the relay is loose, so as to avoid some faults and other accidents in the process of operation.
3. Do not randomly connect the terminal between the Omron relay to the wrong, otherwise it is easy to cause the damage of the Omron relay in power-on operation.
-
202301-09
Schneider frame circuit breaker MT circuit breaker failed to close the switch problem
Schneider structural circuit breaker has not stored energy (check the power supply of the energy storage motor, if normal check whether it can be manually stored energy)MX shunt coil live (disconnect ···
-
202301-06
Fault analysis and maintenance steps of WEINVIEW touch screen failure to turn on
1. The power cable is incorrectly connectedThis may seem obvious, but make sure the power cord is connected to the back of the touch screen and plugged into a power outlet. If it looks connected corre···
-
202302-07
WEINVIEW TK6070ih touch screen into the system setting what are the methods?
1. Generally, there is a small black arrow button in the lower right corner of the touch screen. After clicking and entering the correct password, you can enter the system Settings. However, during co···
-
202307-07
LS PLC use introduction
1, for switching quantity controlThe ability of PLC to control the switching quantity is very strong. The number of points controlled by the input and output points, as few as a dozen points, dozens o···
-
202304-21
Fault detection methods for Omron relays
Fault detection Method One1. You can first check whether the voltage of the Omron relay is high or low. Generally, the maximum voltage is between 180V and 240V.Fault detection Method two2. In addition···