Schneider PLC control cabinet installation wiring method
Published:2023-02-08 16:59:52
(1) When placing signal cables with different properties into the same conduit, they must be isolated
② Try to avoid multiple power lines contained in the same catheter. If necessary, a partition shall be installed in the conduit and grounded.
(3) When wiring with wire tubes, do not place the wires of 1 circuit in different wire tubes because of the heat of wire tubes.
(4) In order not to make the power cable and signal cable mutual influence, do not parallel wiring.
⑤ If installed in the cabinet with high voltage equipment, because the noise will be induced, so as far as possible away from the high voltage, power system wiring Settings.
⑥ Install PLC more than 200mm away from the power line of the high voltage wire, or put the high voltage wire and power wire into the metal pipe wiring, and the metal pipe thoroughly D grounding.
-
202302-07
How do I set the IP address of the touch screen
How to set the IP address when the touch screen is in useFor example: CMT2109X2 and CMT2079XFirst - > Click the little yellow button on the touch screenNext - > Click the lock symbolAgain - >···
-
202302-17
959698 reasons for failure of Siemens 3RW44 soft starter
3RW44 Soft starter 95,96,98 is a comprehensive fault, what causes it to operate?95,96,98 reasons for failure of Siemens 3RW44 soft starter95,96,98 is the normally open normally closed integrated fault···
-
202302-16
Mitsubishi 5U PLC and MCGS touch screen connection
First of all, let's look at the interface Settings of Kunlun touch screen.1. Click the device window to enter Add PLC2. Add a TCP parent serial port and add a 5U device below3. Double-click the pa···
-
202301-31
Delta overload trip fault solution
1. The main cause of VFD overload(1) Mechanical overload. The main characteristic of overload is the motor heating, which can be found by reading the running current on the display screen.(2) The unba···
-
202303-08
Cause of frequent trip of Schneider leakage switch
1. Bad deviceEach pile lead wire is not firmly connected, long-term loose, will cause the pile head heat, oxidation, burn the outer insulation of the wire, and announce the spark and coke taste, the f···